QUESTION: -
ANSWER:
"wipeout.exe" is a DOS application with which you can reset the target
system (S7-200) to the factory default settings. This program is very useful if
you have a target system with an unknown address or baud rate and cannot
communicate with the target system using the STEP 7 Micro/Win. WIPEOUT deletes
•
The user program (OB1)
•
The data block (DB1) and
•
All configuration information (SDB).
The target system is set with address 2 to 9600 baud. WIPEOUT is not installed
in conjunction with STEP 7-Micro/WIN 32. A copy of this application is on the
Installation CD of STEP 7 Micro/WIN 32.
The program can be copied onto the hard disk and then called from there. To call
the program, open the DOS window and enter the "WIPEOUT" command with the
corresponding path. Then follow the prompts on the screen.