The cause could be:
- changed location of the subprojects;
- changed Computer name.
Open multiproject in Component view and select menu View => Detailes
Now look at the fields appeared: UNC path, path on ''Computer'', Computer.
Are the subproject and the library located at that paths?
I can see two solutions:
1. Right click on every subproject and select Multiproject => Remove from Multiproject option.
Then open every subproject separately as it was a single one and select the same option.
Now go back to the multiproject SS1_14_MP and call Multiproject => Insert into Multiproject function, so add the subproject and the library.
2. Open folder: <MultiprojectName> \ <SubprojectName> \ s7extref \
Now you can see two files: s7envref.xml and s7pltref.xml
It is possible to correct them manually.
host_name - is your PC name; shared_path and local_path should be changed according to new projects paths.
The second solution may be quicker if you have many projects on PC and/or in the multiproject too, because it takes much time to open every project. I guess that SIMATIC Manager is always trying to make sure that ALL of the projects in the project list are available.
可以单独打开单项目,移除后重新插入恢复正常;目前文件名称为s7extref\s7pltref.xml