Order No./ Description Component Version
6ES7 315-2AG10-0AB0 Hardware 7
- - - Firmware V 2.6.4
Boot Loader Firmware expansion A 0.21.0
Rack: 0
Slot: 2
Event 1 of 100: Event ID 16# 457F
STOP caused by STOP command
Breakpoint in user program: Startup OB(OB 100)
Priority class: 27
FC number: 100
Module address: 2720
Previous operating mode: STARTUP (warm restart)
Requested operating mode: STOP (internal)
Internal error, Incoming event
04:20:06.214 PM 12/24/2008
Event 2 of 100: Event ID 16# 2522
Area length error when reading
Global DB, word access, Access address: 32
Requested OB: Programming error OB (OB121)
Priority class: 27
Internal error, Incoming event
04:20:06.206 PM 12/24/2008
Event 3 of 100: Event ID 16# 2522
Area length error when reading
Global DB, word access, Access address: 82
Requested OB: Programming error OB (OB121)
Priority class: 27
Internal error, Incoming event
04:20:06.206 PM 12/24/2008
Event 4 of 100: Event ID 16# 2522
Area length error when reading
Global DB, word access, Access address: 130
Requested OB: Programming error OB (OB121)
Priority class: 27
Internal error, Incoming event
04:20:06.205 PM 12/24/2008
Event 5 of 100: Event ID 16# 2523
Area length error when writing
Global DB, word access, Access address: 130
Requested OB: Programming error OB (OB121)
Priority class: 27
Internal error, Incoming event
04:20:06.204 PM 12/24/2008
Event 6 of 100: Event ID 16# 2523
Area length error when writing
Global DB, word access, Access address: 170
Requested OB: Programming error OB (OB121)
Priority class: 27
Internal error, Incoming event
04:20:06.204 PM 12/24/2008
Event 7 of 100: Event ID 16# 2523
Area length error when writing
Global DB, word access, Access address: 168
Requested OB: Programming error OB (OB121)
Priority class: 27
Internal error, Incoming event
04:20:06.203 PM 12/24/2008
Event 8 of 100: Event ID 16# 2523
Area length error when writing
Global DB, word access, Access address: 88
Requested OB: Programming error OB (OB121)
Priority class: 27
Internal error, Incoming event
04:20:06.202 PM 12/24/2008
小程序查看
手机扫码追踪该问题
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
修改FC100后,先不要急着下载,应在线将软冗余块生成的DB块删除,再次进行下载。否则很容易产生I/O Access错误。