Order No./ Description Component Version
6ES7 414-2XK05-0AB0 Hardware 3
- - - Firmware V 5.1.1
Rack: 0
Slot: 2
Event 1 of 120: Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number: 3
DP master system ID: 1
Log. base address of the DP slave: Input address: 8188
Log. base address of the DP master: 8191
Requested OB: Rack failure OB (OB86)
Priority class: 25
External error, Outgoing event
05:17:25.785 PM 11/03/2008
Event 2 of 120: Event ID 16# 39B1
I/O access error when updating the process image input table
P area, double-word access, access address: 12
process image partition no.: 0
not user relevant(Z1): 2942
Requested OB: Program execution error OB (OB85)
Priority class: 25
External error, Incoming event
05:17:25.784 PM 11/03/2008
Event 3 of 120: Event ID 16# 39B1
I/O access error when updating the process image input table
P area, double-word access, access address: 8
process image partition no.: 0
not user relevant(Z1): 2942
Requested OB: Program execution error OB (OB85)
Priority class: 25
External error, Incoming event
05:17:25.784 PM 11/03/2008
Event 4 of 120: Event ID 16# 39B1
I/O access error when updating the process image input table
P area, double-word access, access address: 4
process image partition no.: 0
not user relevant(Z1): 2942
Requested OB: Program execution error OB (OB85)
Priority class: 25
External error, Incoming event
05:17:25.783 PM 11/03/2008
Event 5 of 120: Event ID 16# 39B1
I/O access error when updating the process image input table
P area, double-word access, access address: 0
process image partition no.: 0
not user relevant(Z1): 2942
Requested OB: Program execution error OB (OB85)
Priority class: 25
External error, Incoming event
05:17:25.783 PM 11/03/2008
收藏({{answerDetail.Q_FavoriteCounts}})
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
专家建议
取消最佳答案
修改
是因为你的DP地址为3的那个站丢失引起的,OB86是机架故障,指名了你的那个站丢失,出现的几个OB85也都是因为你的DP3站丢失,引起的I/O通道故障,程序里直接访问这些地址,但是实际找不到这些地址就会出现OB85.
查找你的3号站丢失原因,一般是接地和干扰等原因造成的。下载空的OB85,OB86到CPU中,可以避免停机。