Order No./ Description Component Version
6ES7 315-2AG10-0AB0 Hardware 7
- - - Firmware V 2.6.4
Boot Loader Firmware expansion A 0.21.0
Rack: 0
Slot: 2
Event 1 of 100: Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number: 6
DP master system ID: 1
Log. base address of the DP slave: Input address: 2038
Log. base address of the DP master: 2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
01:27:10.702 AM 02/28/1994
Event 2 of 100: Event ID 16# 456D
STOP caused by program sequence error (OB not loaded or not possible, or no FRB)
Breakpoint in user program: Cyclic program (OB1)
Priority class: 1
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
01:27:08.136 AM 02/28/1994
Event 3 of 100: Event ID 16# 39B2
I/O access error when transferring the process image to the output modules
P area, word access, access address: 17
process image partition no.: 0
not user relevant(Z1): 2943
Requested OB: Program execution error OB (OB85)
Priority class: 26
External error, Incoming event
01:27:08.122 AM 02/28/1994
小程序查看
手机扫码追踪该问题
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
1。仅从诊断提示看,是由于6#DP站点的机架故障引发调用OB86组织块,请求主机架CPU从“RUN”方式转入“STOP”方式。
2。建议先下载一个空的OB86组织块到CPU中,可避免CPU停机。
3。检查6#DP站点的机架是否因电磁阀全部动作后,电源过载导致供电电压太低。
4。逐一检查每个电磁阀动作时外部电源是否短路,而拉垮6#DP站点的机架的电源电压。
5。如果是外部电磁阀电源短路,建议一定要将电磁阀电源与机架电源分离,以免出现6#DP站点机架整体掉电,而引起CPU停机。