L #IN3
ITD
T #TEMP15
L #IN4
ITD
T #TEMP16
A #TEMP11
JCN M001
L #IN2
L #IN0
<D
JC M002
L #IN2
L #IN1
>D
JC M002
JU M003
M001: L #IN2
L #IN0
>D
JC M002
L #IN2
L #IN1
<D
JC M002
JU M003
M002: L 0
T #OUT6
BEC
M003: NOP 0
A #TEMP11
JCN M004
L #IN1
L #IN0
JU M005
M004: L #IN0
L #IN1
M005: -D
L #IN5
/D
T #TEMP8
NOP 0
L #TEMP15
L #TEMP16
<=D
= #TEMP10
A #TEMP10
JCN M006
L #TEMP16
L #TEMP15
JU M007
M006: L #TEMP15
L #TEMP16
M007: -D
L #IN5
/D
T #TEMP9
NOP 0
L 0
T #TEMP12
L #IN0
T #TEMP13
M008: A #TEMP11
JCN M009
L #TEMP13
L #TEMP8
+D
T #TEMP13
L #IN2
<=D
JCN M00a
JC M00b
M009: L #TEMP13
L #TEMP8
-D
T #TEMP13
L #IN2
>=D
JCN M00a
M00b: L #TEMP12
L 1
+D
T #TEMP12
JU M008
M00a: NOP 0
A #TEMP10
JCN M00c
L #TEMP12
L #TEMP9
*D
L #TEMP15
+D
T #OUT6
L #TEMP16
<D
JC M00d
L #TEMP16
T #OUT6
JU M00d
M00c: L #TEMP12
L #TEMP9
*D
T #TEMP14
L #TEMP15
L #TEMP14
-D
T #OUT6
L #TEMP16
>D
JC M00d
L #TEMP16
T #OUT6
M00d: NOP 0
L #OUT6
T #OUT7
收藏({{answerDetail.Q_FavoriteCounts}})
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
专家建议
取消最佳答案
修改
L #IN0
L #IN1
<=D
= #TEMP11//比较in0和in1如果in0小于等于in1,temp11=1
L #IN3
ITD
T #TEMP15//in3转换成双字保存在temp15中
L #IN4
ITD
T #TEMP16//in4转换成双字保存在temp16中
A #TEMP11//如果in0小于等于in1(temp11=1)执行下面的
//程序,否则跳转到m001
JCN M001
L #IN2
L #IN0
<D
JC M002//in2小于in0跳转到m002
L #IN2
L #IN1
>D
JC M002如果in2大于in1跳转到m002
JU M003无条件跳转到m003
M001: L #IN2
L #IN0
>D
JC M002//如果in2大于in0跳转到m002
L #IN2
L #IN1
<D
JC M002//如果in2小于in1跳转到m002
JU M003无条件跳转到m003
M002: L 0
T #OUT6//out6=0
BEC
M003: NOP 0
A #TEMP11//如果in0小于等于in1执行下面程序,否则跳转到
//m004
JCN M004
L #IN1
L #IN0//acc1=in1,acc0=in0
JU M005//无条件跳转到m005
M004: L #IN0
L #IN1
M005: -D
L #IN5
/D
T #TEMP8//temp8=(in0-in1)/in5
NOP 0
L #TEMP15
L #TEMP16
<=D
= #TEMP10/如果temp15小于等temp16,temp10=1否则
//temp10=0
A #TEMP10//如果temp10=1则执行下面的程序,否则跳转到
//m006
JCN M006
L #TEMP16
L #TEMP15//acc1=temp16,acc0=temp15
JU M007//无条件跳转到m007
M006: L #TEMP15
L #TEMP16
M007: -D
L #IN5
/D
T #TEMP9//temp9=(temp15=temp160)/in5
NOP 0
L 0
T #TEMP12//temp12=0
L #IN0
T #TEMP13//temp13=in0
M008: A #TEMP11//如果in0小于等于in1执行下面的程序,否则
//跳转到m009
JCN M009
L #TEMP13
L #TEMP8
+D
T #TEMP13//temp13=temp13+tem8
L #IN2
<=D //如果temp13小于等于in2执行下面的程序否则跳转到
//m00a
JCN M00a
JC M00b//跳转到m00b
M009: L #TEMP13
L #TEMP8
-D
T #TEMP13//temp13=temp13-temp8
L #IN2
>=D //如果temp13大于等于in2执行下面的程序,否则跳转到
//m00a
JCN M00a
M00b: L #TEMP12
L 1
+D
T #TEMP12//temp12=temp12+1
JU M008//无条件跳转到m008
M00a: NOP 0
A #TEMP10//如果temp5<=temp6,执行下面的程序否则跳转到
//m00c
JCN M00c
L #TEMP12
L #TEMP9
*D
L #TEMP15
+D
T #OUT6//out6=temp2*temp9+temp15
L #TEMP16
<D //如果out6<temp16跳转到m00d,否则执行下面的程序
JC M00d
L #TEMP16
T #OUT6//out6=temp16
JU M00d
M00c: L #TEMP12
L #TEMP9
*D
T #TEMP14//tem14=tem12*temp9
L #TEMP15
L #TEMP14
-D
T #OUT6//out6=temp15-temp14
L #TEMP16
>D //如果out6>temp16跳转到m00d否则执行下面的程序
JC M00d
L #TEMP16
T #OUT6//out6=temp16
M00d: NOP 0
L #OUT6
T #OUT7//out7=out6