Order No./ Description Component Version
6ES7 314-1AG13-0AB0 Hardware 1
- - - Firmware V 2.0.12
Rack: 0
Slot: 2
Event 1 of 100: Event ID 16# 49A4
STOP: inconsistency in the configuration data
occurred when checking Parameters for internal consistency
No consistency entries assignable
Error type: parameter field incomplete
Previous operating mode: STARTUP (warm restart)
Requested operating mode: STOP (internal)
External error, Incoming event
02:09:57.639 PM 11/18/2007
Event 2 of 100: Event ID 16# 4301
Mode transition from STOP to STARTUP
STOP due to: STOP caused by stop switch being activated
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
02:09:57.523 PM 11/18/2007
收藏({{answerDetail.Q_FavoriteCounts}})
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
专家建议
取消最佳答案
修改
楼主是在下载后CPU不能运行,还是正常运行过程中CPU停机。但根据上面信息,应是下载完成后不能启动,可能你在下载之前没有编译(不管是程序还是硬件组态),因为如果编译正确(数据一致性就是编译功能来检查)是不会初现楼主所说的CPU错误的。在STEP 7 中重新编译你的项目,看看那个硬件参数设置错误。因为上面信息中提示是参数域没有添全。编译分硬件编译和程序编译你都要检查。