Event 2 of 5: Event ID 16# 530D
New startup information in STOP mode
Startup prevented by:
Loading user program or internal inconsistency detected
(SDBs less than 200 incomplete, supperfluous, or incorrect)
-Cold restart or warm restart necessary
Startup information:
-Time for time stamp at the last non backed up power on
-Single processor operation
Current/last startup type:
-No startup type/following memory reset
Permissibility of certain startup types:
-Manual warm restart permitted
-Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
-Automatic warm restart after non backed up power on (with system memory reset)
Operating mode: STOP(internal)
CP 443网卡Diagnostic buffer:
Event 1 of 5:
Module STOP due to parameter assignment.
我在HARDWARE里编译下装组态后,都启动起来了,正常无报警;但是WINCC里所有的数据都显示未连接上,在网络连接里看,只有和其他工艺CPU连接处于激活,和HMI未激活;在线诊断,硬件无报警,只是CP443,CP443-5EXT下有黑色!号,有经验的帮我分析是什么原因. 非常感谢
收藏({{answerDetail.Q_FavoriteCounts}})
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
专家建议
取消最佳答案
修改
1.按照你提供的诊断信息来看,应该是时间标签“TIME STAMP”的问题。
2.原因有可能是由于CPU中的程序与OS中的变量的时间标签不一致造成的。可能是CPU的程序被你重新下载,但下载的程序是通过备份项目导入的,与OS上的程序不是同一个程序。那么时间标签不一致。也就是说CPU中的程序是A,OS上的程序,变量标签是B,存在差异而造成的。
3.这种情况,你可以尝试以下方法:
3.1重新下载HW,网络,程序到CPU中;
3.2OS重新编译,然后下载到OS站上;
以上的工作是保证OS,CPU中的变量的时间标签保证一致。