For some applications, for example a cooling fan or discharge pump, it is necessary to invert the actual value of the technology controller (PID controller) so that the drive increases the output speed when the PID actual value increases.
How can the control sense of the PID controller be inverted for MICROMASTER 4 / SINAMICS G120 inverters?
Parametrization for MICROMASTER 4 and SINAMICS G120 (independent of the firmware) as follows:
- Is applicable for SINAMICS G120/G120C/G120D/G120P inverters with Control Units with with a “-2” in the product name:
For SINAMICS G120 inverters, the control sense is inverted by reversing the sign of the control difference in parameter p2306 "Technology controller fault signal inversion ". As a result of the conversion, the setpoint is subtracted from the actual value. - Valid for SINAMICS G120/G120D inverters with Control Units without a “-2” in their product name, and for MICROMASTER 4 inverters:
As parameter p2306 for SINAMICS G120/G120D inverters with Control Units CU240S/D and MICROMASTER 4 does not exist, for these inverters, the control sense is inverted by interchanging the setpoint and actual value (p2253 = actual value, p2264 = setpoint). The setpoint is subtracted from the actual value as a result of this interchange.
Note
For details on this topic, see the application example „SINAMICS G120/G120P: Process controls with the technology controller" in Chapter 3, Section 3.1.4 „Technology controller“ entry ID: 92556266
剩余80%未阅读,请登录后下载/查看文档
- 评论
-
分享
扫码分享
- 收藏 收藏
- 点赞 点赞
- 纠错 纠错
- 对于MICROMASTER 4和SINAMICS G120/G120D变频器来说,哪些参数可以通过过程数据区PZD来读取?
- 如何使用MICROMASTER 440 和 SINAMICS G120 的BOP面板来切换手动/自动方式?
- MICROMASTER 4, SINAMICS G120/G120D: “PROFIBUS 参数读/写示例
- MICROMASTER 4 (MM4), SINAMICS G120: 冷却风扇如何运行?
- 用MICROMASTER 440 或 SINAMICS G120电机分级控制
- MICROMASTER 4(MM4),SINAMICS G120x/G110x:变频器序列号的含义
- MICROMASTER 4到SINAMICS G全面升级
- MICROMASTER 4, SINAMICS G110, G110D: 参数p1082的改变
- 如何在HMI面板与变频器之间建立直接连接 (SINAMICS和Micromaster)?
- 如何在 WinCC flexible 或 WinCC (TIA Portal) 项目中插入变频器 (SINAMICS 和 MICROMASTER) 的错误信息?
{{item.nickName}}