找答案的高端用户(找答案钻石及双钻级别的用户)将尽可能从此问题下的所有回
答中,为您推荐最佳答案。届时您可以根据推荐数采纳答案。
如果自提问时间起7天内您仍无法选出最佳答案,您可以选择“无满意答案”关闭此问题。
问题
取消精华
首页精华问答
取消推荐
高端用户推荐
申请置评
已申请置评
修改
修改标签
添加标签
官方认证
取消官方认证
修改标签
添加标签
转移分类
删除
{{itemCategory}}
Diagnostic buffer of module CPU 315-2 DP
Order No./ Description Component Version
6ES7 315-2AG10-0AB0 Hardware 5
- - - Firmware V 2.0.12
Rack: 0
Slot: 2
Event 1 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 18
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:942 am 07/02/08
Event 2 of 10: Event ID 16# 2942
I/O access error, reading
P area, double-word access, Access address: 17
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:942 am 07/02/08
Event 3 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 16
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:941 am 07/02/08
Event 4 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 38
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:941 am 07/02/08
Event 5 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 22
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:940 am 07/02/08
Event 6 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 20
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:937 am 07/02/08
Event 7 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 18
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:936 am 07/02/08
Event 8 of 10: Event ID 16# 2942
I/O access error, reading
P area, double-word access, Access address: 17
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:936 am 07/02/08
Event 9 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 16
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:936 am 07/02/08
Event 10 of 10: Event ID 16# 2942
I/O access error, reading
P area, word access, Access address: 38
Requested OB: I/O access error OB (OB122)
Priority class: 1
External error, Incoming event
07:33:35:935 am 07/02/08
收藏({{answerDetail.Q_FavoriteCounts}})
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
专家建议
取消最佳答案
修改
I/O访问错误组织块(OB122)
描述
只要在访问模块上的数据时出错,CPU的操作系统即调用OB122。例如,如果在访问I/O模块上的数据时,CPU检测到读取错误,操作系统将调用OB122。
了解I/O访问错误OB的操作
执行OB122时所处优先级与中断OB的优先级相同。如果OB122未编程,则CPU将由RUN模式改变为STOP模式。
7提供了下列SFC,用于在执行程序期间屏蔽和取消屏蔽OB122的启动事件:
SFC36 (MSK_FLT):屏蔽特定的错误代码
SFC37 (DMSK_FLT):取消屏蔽由SFC36屏蔽的错误代码
SFC38 (READ_ERR):读取错误寄存器
因为没有加OB122,所以在出现故障时会停机,在块里面添加一个OB122,自己可以建立,空的也没有关系,下载下去后就不会停机了,但是故障一样还是会报,要查一下真正的原因;
我觉得不是站丢失了,如果是站丢失,肯定会要求OB86,并且诊断信息里会报出丢失的站的DP地址,所以不是站丢失。
你的ET200M后面挂的哪些块?要注意如果模拟量模块或者一些特殊功能模块组态地址和在程序中编程地址是不是不一致!
等您来回答
换一换
{{item.CoinValue}}西币
{{item.VisitNum}}人想问
本版相关问题
换一换
专家置评
首次回答问题,获得
双倍西币积分!
立即成为技术知识分享的一员!
欢迎您访问支持中心!
丰富的视频,全方位的文档,大量的网友交流精华……
为了更好的完善这些内容,我们诚邀您在浏览结束后,花20秒左右的时间,完成一个用户在线调查!
感谢您的支持!

官方商城-正品备件
DIOMIS