以上问题后面是怎么解决的,请大师赐教
收藏({{answerDetail.Q_FavoriteCounts}})
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
专家建议
取消最佳答案
修改
27252 PROFIsafe: slave/device %1, bus %2, sign-of-life error
Parameters: %1 = Slave/device identifier
%2 = Bus to which the slave/device is connected.
Explanation: The specified DP slave or the PN device no longer communicates with the master/controller.
Reaction: Mode group not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Triggering of a STOP D/E (settable via MD10097 $MN_SAFE_SPL_STOP_MODE) on all axes with safety functionality.
Stop of the PROFIsafe drivers affected. Stopped PROFIsafe driver of F modules of type F-DI or F-DIO output failsafe
values (0) toward the SPL as F useful data.
Remedy: Check the DP/PN wiring. Restart F modules. Restart the NCK/PLC.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
正常来说,应该是复制安全数据NCK复位,确认安全数据NCK复位
我看你发的图片应该是回传了备份,需要重新坐下安全确认SPL下试试
还有能回传最近期的备份么