Diagnostic buffer of module CP 443-1
Order No./ Description Component Version
6GK7 443-1EX11-0XE0 Hardware 4
- - - Firmware V 2.7.3
Rack: 0
Slot: 4
Event 1 of 8: Event ID 16# F9C1:0255
Netinterface: Automatic setting, AUI with 10 Mbps half duplex
External error, Incoming event
12:00:12.601 AM 01/01/1994
Event 2 of 8: Event ID 16# F9C1:032D
The retentive part of the module database will be erased after loading by the CPU module.
External error, Incoming event
12:00:02.315 AM 01/01/1994
Event 3 of 8: Event ID 16# F9C1:032C
Database now consistent after SDB 1000 was loaded by the CPU containing the SDBs (SDB type 3118)
External error, Incoming event
12:00:02.299 AM 01/01/1994
Event 4 of 8: Event ID 16# F9C1:031C
The SDB 1000 loaded by the CPU containing the SDBs is the consistency assurance SDB (SDB type 3118)
External error, Incoming event
12:00:02.299 AM 01/01/1994
Event 5 of 8: Event ID 16# F9C1:0223
Module STOP due to parameter assignment.
External error, Incoming event
12:00:02.090 AM 01/01/1994
Event 6 of 8: Event ID 16# F9C1:0261
The MAC address was fetched from the boot EPROM. This is the factory setting.
External error, Incoming event
12:00:01.475 AM 01/01/1994
Event 7 of 8: Event ID 16# F9C1:0203
Module database invalid.
Internal cause: 20
External error, Incoming event
12:00:00.388 AM 01/01/1994
Event 8 of 8: Event ID 16# F9C1:0301
No valid configuration data found.
OMS error code: 0
External error, Incoming event
12:00:00.336 AM 01/01/1994
能帮忙看一下是什么原因导致CP443-1不能运行吗?(内部故障灯亮) CPU正常运行,谢谢